Arc suppression is the reduction of sparks formed when current-carrying contacts are separated. The spark is a luminous discharge of highly energized electrons and ions, and is an electric arc.[1][2][3][4]

Uses


(left) Pristine contacts from a relay
(right) The nearly destroyed contacts from a relay operated under power for nearly 100,000 cycles

There are several possible areas of use of arc suppression methods, among them metal film deposition and sputtering, arc flash protection, electrostatic processes where electrical arcs are not desired (such as powder painting, air purification, PVDF film poling) and contact current arc suppression. In industrial, military and consumer electronic design, the latter method generally applies to devices such as electromechanical power switches, relays and contactors. In this context, arc suppression is contact protection.

Arc suppression as contact protection

Every time an electrical power device (for example: heaters, lamps, motors, transformers or similar power loads) turns on or off, its switch, relay or contactor transitions either from a closed to an open state (break arc) or from an open to a closed state (make arc & bounce arc), under load, an electrical arc occurs between the two contact points (electrodes) of the switch. The break arc is typically more energetic and thus more destructive.[5][6]

The energy contained in the resulting electrical arc is very high (tens of thousands of degrees Fahrenheit), causing the metal on the contact surfaces to melt, pool and migrate with the current. The extremely high temperature of the arc cracks the surrounding gas molecules creating ozone, carbon monoxide, and other compounds. The arc energy slowly destroys the contact metal, causing some material to escape into the air as fine particulate matter. This very activity causes the material in the contacts to degrade quickly, resulting in device failure.[4][7]

Arc suppression is an area of interest in engineering because of the destructive effects of the electrical arc to electromechanical power switches, relays and contactors’ points of contact.[8]

Effectiveness

Screen captures from an oscilloscope measuring the arc energy: current shown by blue line (sinusoidal wave), 2V/div = 5A/div; voltage shown by red line,10V/div.
(left) Unsuppressed AC power electrical arc
(right) An identical arc with suppression.

The efficacy of an arc suppression solution for contact protection can be assessed, by comparing the arc intensity with the help of the following methods:

  • Visual Inspection of the arc: The electrical arc can be visually observed on an electromechanical power switch, relay and contactor, with visible contacts, while the contacts are opening and closing under load.
  • Graphical representation of measurements obtained by an oscilloscope: The electrical arc can be observed by using an oscilloscope to trace the voltage wave form across the contact terminals while the contacts are opening and closing under load.[9]

Common devices

Common devices used to prevent arcs are capacitors, snubbers, diodes, Zener diodes, varistors, and transient voltage suppressors.[10] Contact arc suppression solutions that are considered more effective:[11]

  1. Two-wire contact arc suppressor
  2. Solid state relays are not electromechanical, have no contacts, and, thus, do not create electrical arcs.[12]
  3. Hybrid power relays
  4. Hybrid power contactors[13]

Benefits of Arc Suppression

Arc suppression techniques can produce a number of benefits:[14]

  1. Minimised contact damage from arcing and therefore reduced maintenance, repair and replacement frequency.
  2. Increased Contact reliability.
  3. Reduced heat generation resulting in less heat management measures such as venting and fans.
  4. Reduced Ozone and pollutant emissions.
  5. Reduced Electromagnetic Interference (EMI) from arcs - a common source of radiated EMI.

See also

References

  1. Lua error in package.lua at line 80: module 'strict' not found.
  2. Lua error in package.lua at line 80: module 'strict' not found.
  3. A.-M. Howatson, An Introduction to Gas Discharges, Pergamon Press, Oxford pgs. 47-101
  4. 4.0 4.1 Lua error in package.lua at line 80: module 'strict' not found.
  5. The National Association of Relay Manufacturers, Engineers’ Relay Handbook, NARM, 8th Edition, 1980, pg 245
  6. Perry L. Martin, Electronic Failure Analysis Handbook, McGraw-Hill, 1999, pgs. 16.1-16.29
  7. Perry L. Martin, Electronic Failure Analysis Handbook, McGraw-Hill, 1999, pgs. 1.3
  8. Tyco P&B, Contact ARC Phenomenon, Tyco Electronics Corporation – P&B, Winston-Salem, NC, Application Note 13C3203, pgs. 1-3
  9. Lua error in package.lua at line 80: module 'strict' not found.
  10. Tyco P&B, Relay Contact Life, Tyco Electronics Corporation – P&B, Winston-Salem, NC, Application Note 13C3236, pgs. 1-3
  11. Lua error in package.lua at line 80: module 'strict' not found.
  12. The National Association of Relay Manufacturers, Engineers’ Relay Handbook, NARM, 8th Edition, 1980, Chapter 13
  13. Reference Patent Application Publication # 20080266742 assigned to Watlow Electric Manufacturing Company
  14. Lua error in package.lua at line 80: module 'strict' not found.

Further reading